E-mail: sales@hopufiltration.com

Home  >  Product > Transformer Oil Regeneration Machine

Fully Automatic PLC Insulation Oil Regeneration Equipment

Inquire Now Next ProductDownload
share

Product Description

HOPU vacuum transformer oil regeneration system, recycling ,refinery, insulation oil processing purifier Unit

Application
ZY-I Series CE Marked Substation transformer oil recycling system is specially designed for on site use to completely purify and regenerate insulating oils in energized or de-energized transformers. It can regenerate and recycle the old aging transformer oil to approximate new oil. Provide regular oil purification including degassing, drying and particulate removal but also remove acidity, sludge, other soluble oil decay products, and improve color. For special application, the regeneration chamber can be filled with different addtives for decoloring, deacidification, and transformer PCB removal

Fully Automatic PLC Insulation Oil Regeneration Equipment

Oil Regeneration Equipment Features

1. SIEMENS brand PLC, fully automatic operation, big color touch screen display

2. High capacity regeneration chamber installed high pricision filtering elements HOPU designed, can be applied for different additives

3. It provides regular oil purification but also removes acidity, sludge, other soluble oil decay products and discoloration.

4. Degasification, dehydration and filtration processes to purify various kinds of insulation oils in electrical transformers and circuit breakers through one or several passes. 

5. Dielectric loss: tgδ(90 degree)% ≤0.001, Transformer Oil PCB content ≤ 5ppm

6. High vacuum: High point-Vacuum≤5pa Working-vacuum≤35pa

7. High absorption speed: Absorption speed power≥333L/Sr.

8. Duplex 3D stereo-evaporation, eliminating the liquid water quickly

9. UK G technology by which the trace water that is show chain, such as dissolved water, can be removed effectively.

10. Distinctive removing impurities system filtering through double FH trapezoidal network and absorbing by high polymer without the mechanical power

11.  Automatic Anti-Foam Control System, Foam sensor monitoring

12. Specially applied to vacuum oiling and drying for power transmission equipments that are over 110KV

13. The oil of any grades can be treated on line at the working site.

Fully Automatic PLC Insulation Oil Regeneration Equipment

TECHNICAL DATA (specs will be changed when changing requiremnts

ItemUnitZY-I-10ZY--I20ZY-I-30ZY-I-50ZY-I-100ZY-I-150ZY-I-200ZY-I-300
Flow RateL/min10203050100150200300
Vacuum DegreeMPa-0.06 ~ -0.095
Working PressureMPa≤0.4≤0.4≤0.4
≤0.5≤0.5≤0.5≤0.5≤0.5
Temperature Range20-80
Continuous WorkingHour150
Power Supply

380V/ 50HZ/ 3Phase(As per client’s request)
Working NoisedB(A)≤75≤75≤75≤75≤80≤80≤80≤80
Heating Power (OPTIONAL)kW2124263048587085
Total PowerkW22.525.527.533.553657694
Inlet (outlet)Calibermm2525253242505060
Weightkg2302502703005507009501200
After Purification
Breakdown VoltagekV>70
Water ContentPPM<4
Gas Content%<0.1
Particles Sizeμm<3

Fully Automatic PLC Insulation Oil Regeneration Equipment

Optional:

A : Without Enclosure, open and Stationary type

B : With Enclosure, Cubicle and Stationary type

C : With Skid base type

D : Mounted on casters

E : Mounted on Single-axle Trailers (Pneumatic tyre, Speed selectable)

F : Mounted on Double-axle Trailers (Pneumatic tyre, Speed selectable)

Fully Automatic PLC Insulation Oil Regeneration Equipment

You May also be interested in:

A: Transformer Oil Tester, Testing the insulating oil's dielectric strenght

B: Vacuum Pumping Set, pumping the transformer

C: Moisture Meter, measuring the water content in the transformer oil

D: Flow meter, measuring the flow oil quanity through the machine

Hot Products

Contact Us
Follow Us

skype Mobile WhatsApp QQ